The SIESCND69120ANGTH is a Siemens 3-pole, 1200A, 600V LSIG breaker designed for exceptional reliability and protection. With 100% rating capabilities, it ensures optimal performance in demanding applications. Ideal for industrial and commercial use, this circuit breaker provides essential overload, short-circuit, and earth fault protection to safeguard your electrical systems.
| Brand | Siemens |
|---|---|
| Type | Molded-Case (MCCB) |
| Amperage | 1200 A |
| Poles | 3-Pole |
| Voltage | 600V |
| Frame / Series | SIECND |
| Catalogue # | SIESCND69120ANGTH |
The SIESCND69120ANGTH is a Siemens 3-pole, 1200A, 600V molded-case circuit breaker (MCCB) from the SIECND frame series, rated 100% at continuous load with full LSIG trip protection (Long-time, Short-time, Instantaneous, and Ground-fault). As a large-frame industrial MCCB, it is designed for installation in commercial and industrial panelboards, switchboards, and motor control centres — not residential loadcentres.
Mounting and enclosure compatibility varies by installation — send us your switchboard or panelboard details and we'll confirm the fit.
LSIG stands for Long-time, Short-time, Instantaneous, and Ground-fault — the four independent protection functions built into the trip unit of this breaker. Each function is typically adjustable, allowing engineers to precisely coordinate this 1200A breaker with upstream and downstream devices. This is essential in large commercial or industrial distribution systems where selective coordination is required by the Canadian Electrical Code (CEC) to minimize the scope of outages during a fault.
A standard breaker is derated to 80% of its nameplate rating for continuous loads (loads lasting 3 hours or more), meaning a standard 1200A breaker could only serve 960A continuously. The 100% rating on the SIESCND69120ANGTH allows the full 1200A to be used for continuous loads, provided it is installed in a listed enclosure also rated for 100% duty. This can result in a smaller, more cost-effective installation compared to upsizing to a 1600A standard-rated breaker.
Yes — Northern Breaker Group specialises in sourcing obsolete, discontinued, and hard-to-find breakers across Canada. To ensure we source the correct unit or a verified equivalent, have the following ready: the full nameplate part number (SIESCND69120ANGTH), the interrupting rating required for your system, any zone-selective interlocking (ZSI) requirements, and the switchboard or panelboard make and model. Contact us at any of our Calgary, Edmonton, or Vancouver counters or request a quote online.
Looking for pricing, stock or delivery?
Reviews are for product feedback and are not monitored by our sales team. For a price, availability or lead time on this part, send a quote request — we reply from our Calgary, Edmonton and Vancouver counters.
No reviews yet for this product. If you have used it, your feedback helps other trades people choose the right part.